Does the hot tub guidance apply to a holiday let?
HSE's guide is HSG282, the control of legionella and other infectious agents in spa-pool systems (opens in a new tab). HSE's spa-pool systems page (opens in a new tab) says spa pools are a recognised source of disease, including legionnaires' disease. It says outbreaks have been linked to spa pools in leisure centres, hotels, holiday homes and on cruise ships.
HSG282 names holiday lets among the readers it gives guidance to. It sorts hot tubs into three settings:
| Setting | Example HSE gives | What HSG282 says |
|---|---|---|
| Domestic, privately owned | A tub in a private holiday home that is not available for rent or let | Not subject to the Health and Safety at Work etc. Act 1974. Outside the scope of HSG282. |
| Domestic-type, used as a business activity | A tub in a holiday park rental unit, or one provided as part of a rental agreement for a single family or group | Subject to the general duties under the Act. HSE says there is a legal requirement to manage and control it in proportion to the risk. |
| Commercial-type | Hotels and holiday accommodation where the pool is a shared facility | Subject to the general duties under the Act. Designed for higher bather loads, with closer control and monitoring. |
Source: HSG282 (opens in a new tab) paragraphs 2, 75, 76 and 81.
HSE says a domestic-type tub is for a small, discrete group of people at any one time. It says such a tub is unsuitable where several accommodation units share access to one spa pool, for example at a holiday park. A commercial-type spa pool should be used there.
HSG282 says the general duties in the 1974 Act extend to risks from legionella that may arise from work activities. It also points to the Management of Health and Safety at Work Regulations 1999 and the Control of Substances Hazardous to Health Regulations 2002. HSE says only a court can give an authoritative reading of the law. HSE and council inspectors expect employers to follow the approved code of practice or to show they comply in some other way.
HSG282 says HSE and local authorities enforce the law, and that most spa pools in a business setting are enforced by local authorities. This site has not checked which body enforces for a self-catering let.
The risk assessment
HSG282 says the risk assessment should consider the type of pool and how it is used. The design bather load is a key point. HSE says the number of bathers at any time should never exceed the number of seats or loungers in the tub.
The guide says hot tubs are typically kept above 30°C, fitted with air jets and not drained after every use. Small units with regular daily use, and the turnover of water, must be considered in the risk assessment.
HSE describes a domestic-type tub used as a business as one where the water should be changed after each rental or each week, whichever is shorter. It is typically disinfected with bromine or chlorine through an inline disinfectant feeder.
Source: HSG282 (opens in a new tab) paragraphs 70, 76 and 115.
Typical checks for a domestic-type hot tub
HSG282 Table 1 gives typical frequencies for domestic-type spa pools and hot tubs. HSE says the risk assessment should set the actual frequency. These are the domestic-type rows in Table 1.
- At least twice daily, depending on the risk assessment and usage: check water clarity. Measure the pH value and the residual disinfectant.
- Daily: check the dosing system is working. Check the chemical reservoir level where appropriate. Check any automatic systems are working, where fitted.
- As appropriate: record incidents.
- Check daily and clean as appropriate, at least at water replacement: the water line, the overflow channels and skimmers, and the area around the tub.
- Between each group of users or at least weekly, whichever is shorter: drain the tub, clean the whole system including strainers, and refill.
- Between each group of users or weekly, whichever is shorter: check, clean, disinfect and dry the filter cartridge.
- At water replacement: replace the cartridge filter with a cleaned one and inspect the strainers and grilles.
- Weekly: inspect the accessible pipework and jets and clean them as needed. Clean and disinfect the airlines, where appropriate.
- Monthly: disinfect flexible hoses, clean the input air filter and test for ACC, coliforms, E. coli and P. aeruginosa. Where a disinfectant or pH controller is fitted, clean the electrode and check calibration monthly or as the manufacturer instructs.
- Quarterly: test for legionella.
- As the risk assessment sets: a full chemical test, depending on water quality.
Source: HSG282 (opens in a new tab) Table 1 and paragraph 153.
HSG282 says microbiological samples should be taken when the tub is in use, and that the laboratory should be UKAS accredited. Its Table 3 gives a typical range of pH 7.0 to 7.6. It gives 3 to 5 mg/l for chlorine and 4 to 6 mg/l for bromine. Outside wider limits the table says to close the tub and act. Check Table 3 in the guide for those limits.
Records to keep
HSG282 says records must be kept when managing a spa-pool system. It says they should include:
- who did the risk assessment and who manages the controls
- the significant findings of the risk assessment
- the written control scheme
- whether the tub is in use or not
- test results, with dates
- chemical use
- inspections and maintenance
- cleaning and disinfection
- training of anyone who works on the tub
HSG282 says that where there are five or more employees, the law requires the significant findings of the risk assessment to be recorded. It says that with fewer than five employees there is no legal requirement to record anything. It also says a record of the risk assessment must be retained while it remains current and for at least two years afterwards. Monitoring, inspection and test records should be kept for at least five years.
Source: HSG282 (opens in a new tab) paragraphs 51 to 53.
Information for guests
HSG282 says the risk assessment should identify the information for users, usually as a notice. Its example list says bathers should:
- use the toilet and shower before getting in
- keep their head above the water and stay in for no more than 15 minutes at a time
- keep to one bather per seat
- avoid the tub after a heavy meal, alcohol or sedatives
- seek medical advice if pregnant, unwell or immunosuppressed
- supervise children, with no children under 4 or any child who cannot keep their head above the water when seated
Source: HSG282 (opens in a new tab) paragraph 127 and Information box 3.
Hot tub rules by nation
| Nation | What this site found |
|---|---|
| England | HSG282 (opens in a new tab) applies as set out above. This site read no other England page on hot tubs. |
| Wales | HSG282 (opens in a new tab) applies as set out above. This site read no Wales-only page on hot tubs. |
| Scotland | The 1974 Act (opens in a new tab) extends to Scotland, apart from Part III. HSG282 (opens in a new tab) is HSE's guidance on the duties under that Act, and this site found nothing in it that limits it to England and Wales. A licensed short-term let must also assess the risk from Legionella. The Scottish Government guidance (opens in a new tab) says a host can do that assessment themselves and advises keeping a brief record, as the council may want to see it. That advice is about hot and cold water systems, which it says are generally low risk in most residential settings. For hot tubs, pools and spa systems it points separately to HSE's specific guidance. |
| Northern Ireland | Not checked yet. The 1974 Act (opens in a new tab) does not extend to Northern Ireland apart from a few provisions. |
Scotland sources: the Scottish Government guidance paragraphs 2.47 to 2.50, section 84 of the 1974 Act and mygov.scot legal requirements (opens in a new tab). The Scotland licensing page covers the other licence conditions.
How to read this page
- Must and should follow HSE's wording. HSG282 is guidance. Its frequencies are typical, and the risk assessment sets the real ones.
- This site has not checked planning, insurance or electrical rules for hot tubs. See the electrical safety guide for what this site has read on electrics.
- This is general information. It is not legal advice.